Input
|
|
EZ-1: 0.5 to 1.65 GPH
EZ-2: 1.50 to 2.25 GPH
EZ-3: 2.00 to 2.50 GPH |
|
Fuels
|
|
U.S. - No. 1 or No. 2 Fuel Oil
Canada - No. 1 Oil or No. 2 Furnace Oil
|
|
Electrical
|
|
Power: 120 vac, 60Hz, 1-Phase
Current: Approximately 5.8 Amps
Limit Circuit Input: 120 vac, 60 Hz
Motor (PSC): 1/6 HP, 3450 RPM
Motor Frame: 48-Frame, "M" Flange
Oil Valve Power: 120 vac, 60 Hz
Nozzle Line Heater: 120 vac, 60 Hz
Alarm Contacts (Isolated): 24 VAC/VDC, 2 Amps
|
|
Ignition
|
|
Carlin Model 41000 solid state electronic ignition
Ignition Voltage: 14,000 volts |
|
Control
|
|
Carlin Model 60200 Microprocessor Control
15 sec. Trial for Ignition (TFI)
1.3 sec. FFRT
Pre-purge and post-purge (10 seconds)
Serviceman reset protection (Latch-up after three
consecutive lockouts)
Interrupted Duty Ignition
Recycle on flame failure |
|
Operating Temperature Limits
|
|
Maximum Ambient: 104° F (40° C) |
|
Agencies
|
|
UL Listed: US & Canada |